Elena Malyavina, Anastasiya Frolova
The energetic and economic analysis of outdoor temperature to enable the transition to free cooling for conditioned rooms
Conference Information: |
9th International Conference on Environmental
Engineering, MAY 22-24, 2014 Vilnius, LITHUANIA |
Source: |
ICEE-2011 - International Conference on Environmental
Engineering |
Book Series: |
International Conference on Environmental Engineering
(ICEE) Selected papers |
ISSN: |
ISSN 2029-7092 online |
ISBN: |
978-609-457-640-9 / 978-609-457-690-4 CD |
Year: |
2014 |
Publisher: |
Vilnius Gediminas Technical University Press Technika |
View full text in PDF format
Abstract
Energy consumption of electric equipment of free cooling system can't be considered small. On the basis of multiple calculations of
seasonal expenses of the electric power it is shown that expediency of transition to free cooling in Moscow conditions at external air
temperature is near +9 °8. But, an economic comparison of the results found out the profit of transition to a free cooling, which shall be
determined by the dry freezing agent size to be chosen for 100% of a condenser refrigeration load.
Keywords: air-conditioning; cooling machine; sensible-heat cooler; electrical energy; calculation.
|